Guidelines for installation requirements and specifications of cable trays

#公司新闻 ·2026-09-23 14:16:48

1. As a supporting project in wiring engineering, cable trays currently lack specific guidance from specialized specifications. The specifications and models provided by individual manufacturers lack universality. Therefore, during the design and selection process, appropriate trays should be reasonably chosen based on the type and quantity of cables in various weak current systems.

(1) Determine the direction: Determine the routing of cable trays based on the architectural floor plan, taking into account the arrangement of air conditioning and electrical pipelines, ease of maintenance, and the density of cable routes. Indoors, cable trays should be erected along the walls, columns, beams, and floor slabs of the building as much as possible. If utilizing a comprehensive pipe gallery for installation, they should be erected in parallel on one side or above the pipeline, with consideration given to avoiding crossings of down conductors and branch lines. If no other pipe racks are available for use, self-supporting (support) columns need to be established.

(2) Load calculation: Calculate the weight of the cable per unit length on the longitudinal section of the main cable tray trunk line.

(3) Determine the width of the cable tray: Based on the number of cables to be laid, cable diameter, and cable spacing, determine the model and specifications of the cable tray, the length of the support arm, the length and spacing of the pillars, as well as the width and number of layers of the tray.

(4) Determine the installation method: Determine the fixing method of the cable tray based on the setting conditions of the location, selecting from suspended, upright, side-wall, or mixed types. Connectors and fasteners are generally supplied as a set. In addition, select the corresponding cover plate according to the structure of the cable tray.

(5) Draw plan and sectional views of cable trays, and for specific parts, also draw spatial diagrams, and compile a material list.

2. When shared with power cable trays, power cables and low-voltage cables should be placed on opposite sides, with a partition in between.

When weak current cables are shared with other low-voltage cables on the same tray, it is necessary to strictly select weak current cables from weak current systems with external shielding layers to avoid mutual interference.

4. Installation requirements for cable trays

(1) When the trough-type large-span cable tray enters a building from the outside, the outward slope of the tray must not be less than 1/100. (2) When the cable tray crosses over electrical equipment, the clear distance between them must not be less than 0.5m.

(3) When two sets of cable trays are laid in parallel at the same height, the clear distance between them should not be less than 0.6m. (4) Draw the routing of the trays on a parallel diagram, indicating the coordinates or positioning dimensions and elevations of the starting point, end point, turning points, branching points, and elevation changes of the trays. If an axonometric drawing of the tray laying can be drawn, the material statistics will be more accurate.

Straight sections: Indicate the total length, number of tray layers, elevation, model, and specifications. Turning points and branching points: Indicate the model and specifications of the turning adaptor used. Elevation changes: Indicate the elevation changes, which can also be represented by partial detailed drawings or sectional views.

(5) For the support points of the bridge, such as the spacing, installation method, model specifications, and elevation of columns, brackets, or non-standard supports and frameworks, it is acceptable to list them on a plane, or to indicate them in different sections using different sectional views, single-line diagrams, or detailed drawings.

(6) Generally speaking, for the location and method of cable downlead, vertical bending plates and vertical downlead racks can be used for a large number of cables, while guide plates or downlead pipes can be used for a small number of cables. The downlead method should be specified.

(7) Cable trays should be at least 2.2 meters above the ground, with the top of the tray not less than 0.3 meters away from the ceiling or other obstacles. The width of the tray should not be less than 0.1 meters, and the filling rate of the cross-sectional area inside the tray should not exceed 50%.

(8) When laying cables vertically in a cable tray, the upper end of the cable and every 1.5 meters along the way should be fixed to the supports of the tray. When laying horizontally, the beginning, end, turns, and every 3 to 5 meters along the way should be fixed.

(9) When installed within the ceiling, the opening surface of the slot cover should maintain a vertical clearance of 80mm, and the utilization rate of the wire slot cross-section should not exceed 50%.

(10) Cables laid in wire trays can be left unbundled, but they should be kept straight and aligned within the tray, avoiding crossing as much as possible. Cables should not protrude outside the wire tray. At the entrance and exit of the wire tray, as well as at turns, cables should be bundled and secured. Cables laid in vertical wire trays should be fixed to cable supports every 1.5 meters.

(11) When laying cables in horizontal and vertical trays and vertical trunking, the cables should be bundled. For 4-pair cables, bundle them in groups of 24. For trunk cables, optical cables, and other signal cables with 25 pairs or more, bundle them according to the type, diameter, and number of cores of the cables. The bundling spacing should not be greater than 1.5 meters, and the buckle spacing should be uniform with moderate tightness.

(12) When laying the cable tray horizontally, the support spacing is generally 1.5-3m. When laying vertically, the spacing for fixing it to the building structure should be less than 2m.

Selection and laying specifications for cable tray types and varieties

I. Selection of cable tray types and varieties

1. When cable networks requiring shielding against electrical interference or protection against external influences (such as environments with corrosive liquids, flammable dust, etc.) are needed, type (FB) trough-type composite corrosion-resistant shielded cable trays (with covers) should be selected

2. In highly corrosive environments, Class (F) composite epoxy resin anti-corrosion and flame-retardant cable trays should be used. The brackets and supports should also be made of the same material to enhance the service life of the trays and accessories. Cable trays should be covered in environments prone to dust accumulation and other areas that require covering, or in outdoor locations.

3. Apart from the aforementioned situations, tray-type, trough-type, ladder-type, glass anti-corrosion flame-retardant cable trays or steel common-type trays can be selected according to the on-site environment and technical requirements. In environments prone to dust accumulation and other situations requiring covering, or outdoor locations, it is advisable to add cover plates.

4. In public passageways or outdoor road crossings, it is advisable to add base plates at the bottom of the lower rungs or use trays in that section. When crossing public passageways with a large span, the load capacity of the bridge can be increased according to user requirements or a walkway frame can be selected.

5. For large spans (>3m), composite cable trays (FB) should be selected.

6. For outdoor use, composite epoxy resin cable trays (F) should be selected.

II. Selection of cable tray specifications

The width and height of composite epoxy resin cable trays should be selected according to the following table, and should comply with the provisions of relevant standards and specifications regarding cable filling rates. For power cables, a filling rate of 40-50% can be adopted, while for control cables, a filling rate of 50-70% can be adopted. Additionally, a margin of 10-25% should be reserved for future development.

2. The specifications of various elbows and accessories should comply with the engineering layout conditions and be compatible with the cable tray.

3. The selection of support and hanger specifications should be based on conditions such as tray specifications, number of layers, and span, and should also meet the load requirements.

4. The selection of the cross-sectional area of the cable tray is based on the rated current value or setting value (A) of the automatic overcurrent protection for any line in the cable network on the tray, as shown in the table. The allowable values for the cross-sectional area of the tray (mm2) are as follows: 0-60 12961-100 258101-200 452201-400 645401-600 968

III. Configuration of supports and hangers for cable trays

1. Indoor supports and hangers typically have a short span of 1.5-3m. Outdoor columns generally adopt a span of 6m.

2. The configuration of supports and hangers for non-straight sections follows the following principles. When the width of the cable tray is less than 300mm, a support or hanger should be set up on the straight section side, 300-600mm away from the junction of the non-straight section and the straight section. When the width of the cable tray is greater than 300mm, in addition to meeting the conditions below, an additional support or hanger should be added in the middle of the non-straight section.

3. When arranging pultruded fiberglass cable trays in multiple layers, the center-to-center distance between layers should be 200, 250, 300, or 350mm.

4. Expansion joints of 20-30mm should be reserved every 50m along the straight section of the bridge (metal bridge).

IV. Fire prevention: For sections requiring fire prevention, steel or non-combustible and flame-retardant materials shall be used.

V. Grounding of Pultruded FRP Cable Tray

1. The cable tray system should have reliable electrical connections and be grounded (only for metal cable trays).

2. When it is allowed to use the cable tray system to form an earthing main circuit, the following requirements shall be met. The connection resistance between the ends of the cable tray should not exceed 0.00033 ohms, and the insulating coating on the earthing holes should be removed. In a 1KV and below neutral directly grounded system, the earthing of the powered equipment should be connected to the system neutral earthing. When equipped with automatic power cut-off devices, the metal cross-sectional area of the cable tray in the longitudinal direction should not be less than the specified value.

3. When laying a separate grounding main line along the entire length of the cable tray, each section (including non-straight sections) of the cable tray should have at least one point reliably connected to the grounding main line.

4. For vibration sites, spring coils should be installed at the connection points of the grounding parts.

VI. Design content of cable tray system: The engineering design of the cable tray system should be closely coordinated with civil engineering, process engineering, and relevant departments to determine the layout. Its design content may include:

1. Relevant sectional drawings of the cable tray system.

2. Plan layout of the cable tray system.

3. Detailed list of specifications and quantities of straight sections, bends, supports, and hangers required for the cable tray system, along with necessary explanations.

4. Technical descriptions or schematic diagrams of non-standard components with special requirements.

VII. Installation: For the installation of cable trays, please refer to the nationally applicable building standard design - electrical installation standard atlas "Cable Tray Installation" issued by the China Building Standard Design and Research Institute.

VIII. Design Requirements

1. Path layout plan of the bridge system;

2. Relevant cross-sectional drawings of the bridge system.

3. A detailed list of the anti-corrosion materials used in the bridge system, as well as the specifications and quantities of the required straight through, bent through, supports (hangers), etc., along with necessary descriptions. The connecting plates, screws, and protective caps shall be fully equipped by the manufacturer according to the above requirements.

4. Non-standard technical specifications or diagrams with special requirements.

1. Selection of cable tray types and varieties

1. When cable networks requiring shielding against electrical interference or protection from external influences (such as environments with corrosive liquids, flammable dust, etc.) are needed, Class (FB) trough-type composite anti-corrosion shielded cable trays (with covers) should be selected.

2. In strongly corrosive environments, Class (F) composite epoxy resin anti-corrosion flame-retardant cable trays should be used. The brackets and supports should also be made of the same material to enhance the service life of the trays and accessories. Cable trays should be covered in environments prone to dust accumulation and other areas requiring covering, or in outdoor locations.

3. Apart from the above situations, tray-type, trough-type, ladder-type, glass anti-corrosion flame-retardant cable trays or steel ordinary-type trays can be selected according to the on-site environment and technical requirements. Cable trays should be covered in environments prone to dust accumulation and other areas requiring covering, or in outdoor locations.

4. In public passages or outdoor road crossings, base plates should be added to the bottom of the bottom rungs or trays should be used in those sections. When crossing public passages with large spans, the load capacity of the trays can be increased according to user requirements or pedestal frames can be selected.

5. For large spans (>3m), composite trays (FB) should be selected.   

6. For outdoor use, composite epoxy resin cable trays (F) should be selected.

II. Specification selection

1. The width and height of the cable tray should be selected according to the following table, and should comply with the provisions of relevant standards and specifications regarding cable filling ratio. For power cables, a filling ratio of 40-50% can be adopted, while for control cables, a filling ratio of 50-70% can be adopted. Additionally, a margin of 10-25% for future development should be reserved.   

2. The specifications of various bends and accessories should comply with the engineering layout conditions and match the cable tray.   

3. The selection of support and hanger specifications should be based on the tray specifications, number of layers, span, and other conditions. It should also meet the load requirements.   

4. The selection of cable tray cross-sectional area is shown in the table.   Rated current value or setting value (A) of automatic overcurrent protection for any line in the cable network on the tray   Allowable tray cross-sectional area (mm2)   0-60 129   61-100 258   101-200 452   201-400 645   401-600 968

III. Configuration of supports and hangers

1. Indoor supports and hangers typically have a short span of 1.5-3m. Outdoor columns generally have a mid-span of 6m.

2. The configuration of supports and hangers for non-straight sections follows the following principles. When the width of the cable tray is less than 300mm, a support or hanger should be set up on the straight section side, 300-600mm away from the junction of the non-straight section and the straight section. When the width of the cable tray is greater than 300mm, in addition to meeting the conditions below, an additional support or hanger should be added in the middle of the non-straight section.

3. When setting up multiple layers of cable trays, the center-to-center distance between layers should be 200, 250, 300, and 350mm.

4. Expansion joints of 20-30mm should be reserved every 50m along the straight section of the bridge (metal bridge).   

IV. Fire Prevention

For sections requiring fire protection for cable trays, steel or non-combustible and flame-retardant materials are used. The BJIII series cable trays produced by our company are all fire-resistant trays.

V. Grounding

1. The cable tray system should have reliable electrical connections and be grounded (only for metal cable trays).

2. When utilizing the cable tray system to form an earthing main circuit, the following requirements must be met. The connection resistance between the ends of the cable tray should not exceed 0.00033 ohms, and the insulating coating on the earthing holes should be removed. In a 1KV and below neutral point direct grounding system, the earthing of the powered equipment should be connected to the system's neutral line earthing. When equipped with automatic power cut-off devices, the metal cross-sectional area of the cable tray in the longitudinal direction should not be less than the specified value.

3.When laying additional grounding main lines along the entire length of the cable tray, each section (including non-straight sections) of the cable tray should have at least one point reliably connected to the grounding main line.

4. For vibration sites, spring coils should be installed at the connection points of the grounding parts.

VI. Design content of bridge system

The design of the bridge system engineering should be closely coordinated with civil engineering, process engineering, and relevant departments to determine the layout. Its design content may include:

1. Relevant sectional drawings of the bridge system.

2. Plan layout of the bridge system.

3. A detailed list specifying the specifications and quantities of straight sections, bends, supports, and hangers required for the cable tray system, along with necessary explanations.

4. Technical specifications or schematic diagrams for non-standard parts with special requirements.

VII. Installation

For the installation of cable trays, please refer to the nationally applicable building standard design - electrical device standard atlas "Cable Tray Installation" 04D701-3 issued by the China Building Standard Design and Research Institute.

VIII. Design Requirements

1. Path layout plan of the bridge system;

2. Relevant sectional drawings of the bridge system.

3. A detailed list specifying the anti-corrosion materials used in the bridge system, as well as the specifications and quantities of necessary straight throughs, bends, supports (hangers), etc., along with the necessary descriptions. The connecting plates, screws, and protective caps shall be fully equipped by the manufacturer according to the above requirements.

4. Non-standard technical specifications or diagrams with special requirements.