Cable tray design standards

#公司新闻 ·2026-09-23 14:17:31

I. Selection of cable tray types and varieties

When there is a need to shield cable networks from electrical interference or when there are requirements for protection against external influences (such as environments with corrosive liquids, flammable dust, etc.), type (FB) trough-type composite corrosion-resistant shielded cable trays (with covers) should be selected

2. In highly corrosive environments, Class (F) composite epoxy resin anti-corrosion and flame-retardant cable trays should be used. The support arms and brackets should also be made of the same material to enhance the service life of the trays and accessories. Cable trays should be covered in environments prone to dust accumulation and other situations requiring covering, or in outdoor locations. 3. Except for the above situations, tray-type, trough-type, ladder-type, glass anti-corrosion and flame-retardant cable trays or steel ordinary-type trays can be selected according to the on-site environment and technical requirements. Cable trays should be covered in environments prone to dust accumulation and other situations requiring covering, or in outdoor locations.    

4. In public passageways or outdoor road crossings, it is advisable to add base plates at the bottom of the lower rungs or use trays in this section. When crossing public passageways with a large span, the load capacity of the bridge can be increased according to user requirements or a walking frame can be selected.    

5. For large spans (>3m), composite cable trays (FB) should be selected.    

6. For outdoor use, composite epoxy resin cable trays (F) should be selected.    

II. Specification selection

1. The width and height of the cable tray should be selected according to the following table, and should comply with the provisions of relevant standards and specifications regarding cable filling ratio. For power cables, a ratio of 40-50% can be adopted, while for control cables, a ratio of 50-70% can be adopted. Additionally, a margin of 10-25% should be reserved for future development.    

2. The specifications of various bends and accessories should comply with the engineering layout conditions and be compatible with the cable tray.    

3. The selection of support and hanger specifications should be based on conditions such as cable tray specifications, number of layers, and span. It should also meet the load requirements.    

4. Selection of tray cross-sectional area is shown in the table. The rated current value or setting value (A) of automatic overcurrent protection for any line in the cable network on the tray. Allowable tray cross-sectional area (mm2) 0-60 129 61-100 258 101-200 452 201-400 645 401-600 968

III. Configuration of supports and hangers

1. The short span for indoor supports and hangers is generally 1.5-3m. The mid-span for outdoor columns is generally 6m.

2. The configuration of supports and hangers for non-straight sections follows the following principles. When the width of the cable tray is less than 300mm, a support or hanger should be set up on the straight section side, 300-600mm away from the junction of the non-straight section and the straight section. When the width of the cable tray is greater than 300mm, in addition to meeting the conditions below, an additional support or hanger should be added in the middle of the non-straight section.    

3. When setting up multiple layers of trays, the center-to-center distance between layers should be 200, 250, 300, and 350mm.

4. Expansion joints of 20-30mm should be reserved every 50m along the straight section of the bridge (metal bridge).    

IV. Fire Protection Requirements: For the fire-resistant sections of cable trays, steel or non-combustible and flame-retardant materials shall be used. The BJIII series cable trays produced by our company are all fire-resistant trays.  

V. Grounding

1. The cable tray system should have reliable electrical connections and be grounded (only for metal cable trays).    

2. When utilizing the cable tray system to form an earthing main circuit, the following requirements must be met. The connection resistance between the ends of the cable tray should not exceed 0.00033 ohms, and the insulation coating on the earthing holes should be removed. In a 1KV and below neutral point direct grounding system, the earthing of the powered equipment should be connected to the system's neutral line earthing. When equipped with automatic power cut-off devices, the metal cross-sectional area of the cable tray in the longitudinal direction should not be less than the specified value.   

3. When laying a separate grounding main line along the entire length of the cable tray, each section (including non-straight sections) of the cable tray should have at least one point reliably connected to the grounding main line.

4. For vibration sites, spring coils should be installed at the connection points of the grounding parts.    

VI. Design Content of the Cable Tray System The design of the cable tray system should closely cooperate with civil engineering, process engineering, and relevant departments to determine the layout. Its design content may include:

1. Relevant sectional drawings of the bridge system.    

2. Plan layout of the bridge system.    

3. A detailed list of specifications and quantities of straight sections, bends, supports, and hangers required for the cable tray system, along with necessary explanations.    

4. Technical specifications or schematic diagrams for non-standard parts with special requirements.    

7. Installation. For the installation of cable trays, please refer to the nationally applicable building standard design - electrical device standard atlas "Cable Tray Installation" 04D701-3 issued by the China Building Standard Design and Research Institute.    

VIII. Design Requirements

1. Path layout plan of the bridge system;    

2. Relevant sectional drawings of the bridge system.    

3. A detailed list specifying the anti-corrosion materials used in the bridge system, as well as the specifications and quantities of straight throughs, bends, supports (hangers), etc. required, along with necessary explanations. The connecting plates, screws, and protective caps shall be fully provided by the manufacturer according to the above requirements.    